40G Ceritfier Copper Test Failures

Martes, Diciembre 31, 2019
Enviado por ryan.grace el Julio 8, 2021 - 4:41pm
Problem: 
My copper tests keep failing on my Certifier 40G. What can I do to troubleshoot?
Solution: 
First make sure the correct limit is selected for the type of copper cabling that you are testing. Second make sure a proper reference was performed and if necessary re-reference the units. Check all connections at panel and jack fields. Wire should only be untwisted just enough to perform the termination and no more. Use the fault locator graph, on the cable test results, to identify the distance to the worst result which is most likely a connection of some type and re-terminate. If permanent link testing, check the probe count under the SYSTEM SETTINGS>SETTINGS 2DEVICE INFO. Viavi recommends that permanent link adapter cords be replaced after 5000 tests.

Product Family:

Asistencia en cada paso

Proporcionamos soporte técnico, servicios, una formación completa y los recursos que necesita. Todo ello forma parte de lo que hacemos con el fin de maximizar el valor de su inversión en VIAVI.

Valor y servicios que complementan su catálogo de instrumentos y soluciones de sistemas VIAVI para proporcionar un coste total de propiedad excelente

Ofrecemos un servicio de atención al cliente que proporciona solicitudes de autorización de devolución de material (RMA) para tareas de reparación y calibración

Soluciones educativas técnicas, formación sobre productos y una formación combinada para técnicos que utilizan productos nuevos o trabajan con herramientas existentes

El centro de asistencia técnica (TAC) le ayudará a utilizar y configurar los productos y se encargará de los problemas relativos al rendimiento del producto