40G Certifier Limit Selection

Monday, June 26, 2023
Submitted by ryan.grace on April 4, 2024 - 8:37pm
Problem: 
Which limit should be selected, on the 40G Certifier, if there are different categories of cabling in the path to be tested?
Solution: 
The lowest rated cable type, in the circuit path, determines the level you should test at. Example: The permanent link is 6A but the wired channel connections are CAT6 then a CAT6 limit should be selected when performing channel testing that includes the CAT6 cabling.